Kapacitný limitný spínač výšky hladiny LNZ

| aj pre elektricky nevodivé kvapaliny | |
| citlivý na penu,nevhodné pre pri3/4navé materiály | |
| Prípoj | G 1/2 |
| hygienický systém montáže (EHEDG) | |
| hygienická norma DIN 11851, Tri-Clamp,pomocný prípoj | |
| Materiál | ušlachtilá ocel 1.4404 / PEEK |
| Max. tlak | 10 bar |
| Max.teplota | 100 °C (CIP 150°C) |
| Kontakt | Otvorený kolektor, PNP, 200 mA |
The LNZ capacitive level switch is used for detecting levels of fill. The electric field penetrates several millimetres into the medium. The change in capacity caused by contact with the medium is measured and evaluated. By using this principle of measurement it is also possible to detect non-conductive media. Installation in tanks is very straightforward regardless of position. In combination with the KOBOLD LZE or LZE-R weld-in sleeves, the probe provides a measuring point that has no dead space and meets hygiene standards and (EHEDG approval certificate). Installation is virtually front-flush. This level switch is therefore very well suited for CIP/SIP cleaning. Adapter sleeves are also available for different process connections so that the device can also be used in existing systems. Because the electronics are already integrated no other evaluating instrument is necessary. The output signal (24 VDC ) can therefore be transmitted direct to an SPS for further processing.