Please select your country

Please select your language

 
Kobold Messring GmbH > Level  > Capacitive Level Limit Switch LNZ

Capacitive Level Limit Switch LNZ

Capacitive  Level Limit Switch LNZ
As well for non conductive liquids
sensitive to foam, not for adhesions
Connection G 1/2
hygenic mounting system (EHEDG)
hygenic DIN 11851, Tri-Clamp, weld on sleeve
Material st.st. 1.4404 / PEEK
Max. pressure 10 bar
Max. temperature 100 °C (CIP 150°C)
Contact Open Collector, PNP, 200 mA
The LNZ capacitive level switch is used for detecting levels of fill. The electric field penetrates several millimetres into the medium. The change in capacity caused by contact with the medium is measured and evaluated. By using this principle of measurement it is also possible to detect non-conductive media. Installation in tanks is very straightforward regardless of position. In combination with the KOBOLD LZE or LZE-R weld-in sleeves, the probe provides a measuring point that has no dead space and meets hygiene standards and (EHEDG approval certificate). Installation is virtually front-flush. This level switch is therefore very well suited for CIP/SIP cleaning. Adapter sleeves are also available for different process connections so that the device can also be used in existing systems. Because the electronics are already integrated no other evaluating instrument is necessary. The output signal (24 VDC ) can therefore be transmitted direct to an SPS for further processing.